Specification of KWH Meter MK6E
Kwh MeterAccuracy
• Class 0.2S (IEC62 053-23)
Voltage
• Nominal - 57.7/100V - 230/400V
(phase to neutral)
• Burden - <10VA / phase @ Vn (3
phase)
• Frequency 45-65 Hz
Current
• CT Range - 1/4A and 5/10A
• Short time over-current - 20 times
the Imax for 0.5 seconds
• Burden - <0.5VA/phase
Auxiliary Supply Options
• 240V, 110V (other voltages available
on special order)
Measurement Modes
• 3 phase 3 wire (2 element)
• 3 phase 4 wire (3 element)
Measured Energy Values
• Import/Export Wh, varh and VAh
• Absolute Wh, varh and VAh
• 4 quadrant Wh, varh and VAh
• Phase A, B, C or Total
Other Measured and Displayed
Values
• Power: W, var, VA
• True RMS Voltage (3 phase)
• True RMS Current (3 phase)
• Power factor
• Frequency
• Phasor angles
Quality of Supply Features
• THD
• Unbalance
• Fundamental Voltage, Current and
Watt measurement
• Harmonics (up to the 50th)
• Sag / Swell
- 5 cycle resolution
- Records time/date/phase/duration
/worst excursion
- Programmable trigger levels
Pulsing IO
• 2 inputs + common ground
• 2 outputs + common ground
• 6 outputs + common ground
• 110/240V BOSFET outputs
(IEC 62053-31 class A and B)
• Up to 16 inputs or outputs via
optional extended IO cards
Communications Ports
• Local - ANSI type 2 optical or
FLAGTM (IEC 61107)
• Remote - Isolated RS485, RS232
or both
Communications Features
• ANSI Type 2 Optical
• IEC 61107 / IEC 62056-21
+ VDEW 2.0 extensions
• RS232 (RTS/CTS and DTR/DCD)
• RS485 (2 or 4 wire multidrop)
• SCADA
• Modems
(PSTN/GPRS/GSM/CDMA)
• MV90TM
• MODBUS®
• UDP/IP over PPP/GPRS
• DNP3 level 2
• IEC 870-5-102
• Optional internal modem
power supply
Temperature Range
• Operating -25 to +60°C
• Storage -25 to +80°C
Humidity range
• 0 to 95% non condensing
Time Keeping
• Accuracy: 0.5s/day (over full
temperature range)
• Backup time - 2 years
without power
• Backup type - optional lithium
battery 700/1200mAh, 3.6V and
SuperCap (single/dual)
• Battery shelf life of 20 plus years
• Mains synchronised or internal
crystal time keeping. Mains
synchronised reverts to internal
crystal on loss of all phase volts
Time Of Use
• 8 rates plus unified rate
• Up to 12 separate import and
export registers
• Up to 200 programmable
special days
• Daily, Weekly, Monthly,
Yearly, Special
• 13 or more previous periods
• Block or Rolling Maximum Demand
• Time of Maximum Demand
Load Survey / Profile
• NEM compliant
• Over 900 kilobytes of fl ash data
storage space.
~ 3100 day-channel capacity at 30
minute intervals
~ 1875 day capacity at 30 minute
intervals / 2 channels
~ 520 day capacity at 15 minute
intervals / 3 channels
• Up to 50 channels
• Interval programmable from 1
second to 1 month
• Multiple independent surveys
• Energy, instantaneous readings,
pulsing inputs, average/min
/max readings
LCD Display
• 16 character by 2 line
alphanumeric display
• Programmable units, multipliers
and leading zeros
• Up to 64 user definable
screen displays
• Displays any available
meter parameter
• Optional 20 character by 4 line
alphanumeric display
Extensions for Customer
Applications: standard or to
order
Mk6E GENIUS plus®meter
continues the successful concept
of meter “Extensions” introduced
in the original Mk6 Genius® Using
“EziScript”, complex register
manipulations can be performed
allowing sophisticated meter
functions. New Extensions are
constantly under development,
contact us to find out the
latest updates.
Some examples of currently available
Extensions are:
• Send SMS at percentage of
maximum demand, or equipment
failure alarm
• Maximum demand control of loads
via pulsing outputs
• Time Of Use history etc
Software
• EziView Windows® software
(optional), can be used for
programming and reading
the meter
• EziView also allows offline
configuration of tariff programs
and all meter parameters, for
later upload
Dimensions
• 262mm (L) 175 mm (W) 93mm (D)